Weak-grid, SSO & impedance-based stability studies
Converter controls on a weak or series-compensated grid can produce oscillations that barely die out, often below 50 Hz. We find them with impedance scans and a Nyquist check, then prove them in the time domain.
When you need it.
- A converter plant connects to a weak grid or near series compensation.
- The area is dense with converters, so control interactions are more likely.
- The operator wants impedance or stability screening for the connection.
- Oscillations have been seen on site and the cause needs finding.
The Nyquist check, before and after.
Choose a case to see the result.
How we run it.
- 01
Scan
Get converter and grid impedance across frequency, in dq or sequence domain.
- 02
Screen
Use a Nyquist check to find marginal or unstable conditions.
- 03
Confirm
Inject at the flagged frequencies in EMT to prove the mode is real.
- 04
Bound
Vary grid strength, dispatch and unit count to bound the risk.
- 05
Fix
Recommend changes where damping is poor, and check they work.
Every scenario through every study.
- Impedance scan toolsFrequency domain
- PSCADTime domain
- Vendor control modelsConverters
Series compensation levels · Frequency scanAt 35% compensation the resistance turned negative near 30 Hz. A damping controller restores it.Line outages · Nyquist checkWith one line out the Nyquist plot passed close to −1. Retuned current control restores the margin.Nearby converters · Damping checkTwo plants shared a 7 Hz mode. Coordinated gains raise its damping above 5%.
What you get.
- ReportImpedance and stability report with the modes and margins found
- EvidenceNyquist plots and the EMT waveforms that confirm them
- FixesRecommended changes, each checked in the model
- MethodMethod, assumptions and model sources, written down
How we check it
Screening and time-domain runs are checked against each other, so a flagged mode is shown, not guessed. The conditions that decide stability are stated plainly for the reviewer.
Questions engineers ask.
What is subsynchronous oscillation in inverter-based systems?
Why use impedance methods first?
Can settings fix an SSO problem?
Have a study like this coming up?
Related: Consultancy hub · Control interaction studies · 40 MW battery case study · PSCAD / EMT studies